Skip to main content
Cheat SheetCELE · Reinforced & Prestressed Concrete

CELE Reinforced & Prestressed Concrete — Reinforced Concrete SlabsCheat Sheet

A cheat sheet for Reinforced Concrete Slabs (CELE Reinforced & Prestressed Concrete): definitions, formulas and must-remember facts in one place.

Reinforced Concrete Slabs - Cheat Sheet

Your 30-minute final review for one-way and two-way slab design, minimum thickness, flexural steel, shrinkage/temperature reinforcement, and coefficient/DDM methods. All formulas, classifications, and board-exam pitfalls in one place.

One-Way vs Two-Way Classification

Formulas

Aspect Ratio = L_long / L_short

Meaning

L_long = longer span; L_short = shorter span; both measured center-to-center of supports

Watch out

Do NOT use short/long backward; always divide LONGER by SHORTER. A slab on only two opposite sides is ALWAYS one-way, regardless of ratio.

When to use

Every slab design starts here — classify before choosing method

Important facts

  • If aspect ratio is exactly 2.0, classify as TWO-WAY (≥ 2 means one-way; < 2 means two-way).
  • Two-way slabs on columns (flat plates) use Direct Design Method (DDM) or Equivalent Frame Method.
  • Two-way slabs on stiff beams use Coefficient Method with tabulated moment coefficients.
  • All four edges supported is required for true two-way behaviour; cantilever or three-sided support → one-way.

Key definitions

One-Way Slab

Example

5 m × 2.4 m panel (5/2.4 = 2.08 ≥ 2) → one-way; or a 6 m cantilever off a beam → one-way.

Rectangular slab with L_long/L_short ≥ 2, or supported on only two opposite sides; bends primarily across the short span; designed as 1 m strip.

Two-Way Slab

Example

4 m × 3.5 m panel (4/3.5 = 1.14 < 2) → two-way slab on beams.

Rectangular slab with L_long/L_short < 2, supported on all four sides; bends in both directions; uses coefficient or DDM/EFM.

Diagrams to know

  • Aspect ratio decision tree: L_long/L_short ≥ 2? → one-way; < 2 → two-way.
  • Support configuration diagram: four-sided vs two-sided vs cantilever.

Minimum Thickness (Deflection Control)

Formulas

h_min = L / C

Meaning

L = clear span or effective span (NSCP 2015); C = coefficient based on support condition

Watch out

This h_min applies to SOLID slabs only. Use clear span, not center-to-center. If f_y ≠ 420 MPa, multiply by adjustment factor.

When to use

Whenever designing a one-way slab; if h ≥ h_min, deflection checks may be skipped

h_min (adjusted) = (L/C) × (0.4 + f_y/700)

Meaning

Adjustment factor for yield strength not equal to 420 MPa; f_y in MPa

Watch out

The adjustment is multiplicative. For f_y = 415 MPa: factor = 0.4 + 415/700 = 0.993; for f_y = 275: factor = 0.4 + 275/700 = 0.793.

When to use

When f_y = 275, 380, 415, or other non-standard value

Common values

Value

415 MPa

Symbol

f_y

Quantity

Standard yield strength

Value

275 MPa

Symbol

f_y

Quantity

Older/lower yield

Value

28 MPa (f'_c)

Symbol

f'_c

Quantity

Concrete strength (typical)

Important facts

  • Use CLEAR SPAN (face-to-face of supports) or effective span per NSCP 2015.
  • For prestressed slabs, h_min is reduced — consult NSCP or ACI 318.
  • If actual h < h_min, perform deflection check per NSCP Section 421.5.3.
  • Continuous slabs allow thinner sections because negative moments are smaller.
  • Always check that chosen h satisfies both minimum thickness AND provides adequate concrete cover (typically 20–40 mm).

Key definitions

Simply Supported (SS)

Example

Span 3.5 m, f_y = 415 → h_min = (3500/20) × 0.993 = 174 mm.

Slab resting on supports at two ends; no moment continuity; h_min = L/20.

One End Continuous (1EC)

Example

Span 4.0 m, f_y = 415 → h_min = (4000/24) × 0.993 = 165 mm.

One end fixed, one end simply supported; h_min = L/24.

Both Ends Continuous (2EC)

Example

Span 4.2 m, f_y = 415 → h_min = (4200/28) × 0.993 = 149 mm.

Both ends fixed to beams or walls; h_min = L/28.

Cantilever

Example

Cantilever overhang 1.2 m, f_y = 415 → h_min = (1200/10) × 0.993 = 119 mm.

Slab projecting beyond support; h_min = L/10 (much thicker than spanning slabs).

Diagrams to know

  • Minimum thickness table by support condition and f_y.
  • Adjustment factor curve for f_y vs (0.4 + f_y/700).

Flexural Design (One-Way, Per-Metre Strip)

Formulas

R_n = M_u / (φ × b × d²)

Meaning

R_n = nominal resistance factor (MPa); M_u = factored moment (N·mm); φ = 0.90 for flexure; b = 1000 mm (per-metre width); d = effective depth (mm)

Watch out

Convert M_u to N·mm if given in kN·m: M_u(N·mm) = M_u(kN·m) × 10⁶. Keep units consistent.

When to use

Always step 1 in slab flexural design; compute from factored moment

ρ = (0.85 × f'_c / f_y) × [1 − √(1 − (2 × R_n) / (0.85 × f'_c))]

Meaning

ρ = steel ratio (unitless); f'_c = concrete strength (MPa); f_y = yield strength (MPa); R_n from previous formula

Watch out

Do NOT use ρ_max; this formula gives ρ directly. If R_n is too large, the square root becomes imaginary → section is under-reinforced and moment capacity is insufficient.

When to use

Calculate ρ after finding R_n; this is the balanced ratio approach (NSCP/ACI 318)

A_s = ρ × b × d

Meaning

A_s = required steel area (mm²/m, per metre width); ρ = steel ratio; b = 1000 mm; d = effective depth (mm)

Watch out

A_s is in mm²/m — this is the area needed across a 1-metre-wide strip. Must check against shrinkage/temperature minimum.

When to use

Final step to get steel per metre; convert to bar spacing next

s = (A_b × 1000) / A_s

Meaning

s = bar spacing (mm, center-to-center); A_b = area of ONE bar (mm²); A_s = required area per metre (mm²/m)

Watch out

Spacing must satisfy s ≤ min(3h, 450 mm) for main steel. If s_calculated < min, reduce spacing; if > min, use min.

When to use

Convert per-metre steel to practical bar spacing for detailing

Common values

Value

1000 mm

Symbol

b

Quantity

Per-metre strip width

Value

20–40 mm

Symbol

cover

Quantity

Concrete cover (beams/slabs)

Value

78.5 mm²

Symbol

A_φ10

Quantity

10 mm φ bar area

Value

113.1 mm²

Symbol

A_φ12

Quantity

12 mm φ bar area

Value

201.1 mm²

Symbol

A_φ16

Quantity

16 mm φ bar area

Important facts

  • Minimum steel ratio: ρ_min = max(0.0014, 1.4 × f_y / f'_c); but shrinkage/temperature steel often governs.
  • For thin slabs with low moments, shrinkage/temperature minimum (ρ_temp = 0.0018) typically controls A_s.
  • Always check A_s ≥ A_s,min; if not, use minimum and adjust spacing downward.
  • Maximum steel ratio ρ_max ≈ 0.75 × ρ_balanced; over-reinforced sections fail suddenly (not acceptable).
  • Bar spacing cannot exceed min(3h, 450 mm) for main steel; if spacing too large, add bars.

Key definitions

Per-Metre Strip Design

Example

A slab with A_s = 315 mm²/m and 10 mm φ bars (A_b = 78.5 mm²) requires s = 78.5 × 1000 / 315 = 249 mm spacing.

One-way slab analyzed as a 1 m wide rectangular beam with b = 1000 mm; all calculations (M_u, R_n, A_s) per unit width.

Effective Depth (d)

Example

h = 175 mm, cover = 20 mm, bar diameter 10 mm → d = 175 − 20 − 5 = 150 mm.

Distance from extreme compression fibre to centroid of tension steel; d = h − cover − φ_bar/2.

Diagrams to know

  • Flow chart: M_u → R_n → ρ → A_s → spacing s.
  • Cross-section of slab showing h, cover, d, and bar positions.

Shrinkage & Temperature Steel

Formulas

A_s,temp = ρ_temp × b × h

Meaning

A_s,temp = minimum steel perpendicular to main steel (mm²/m); ρ_temp = shrinkage/temperature ratio; b = 1000 mm (per metre); h = slab thickness (mm)

Watch out

Use FULL thickness h, not effective depth d. This is a separate, minimum requirement — always check. ρ_temp varies with f_y.

When to use

EVERY slab design must provide temperature steel perpendicular to main flexural steel

ρ_temp = 0.0018 (for f_y = 415–420 MPa); ρ_temp = 0.0020 (for f_y = 275 MPa)

Meaning

Shrinkage/temperature ratio specified by NSCP based on steel grade

Watch out

Do NOT confuse with main flexural steel ratio ρ. Temperature steel is a code minimum independent of moment.

When to use

Plug into A_s,temp formula; standard values per NSCP 2015

s_temp = (A_b × 1000) / A_s,temp

Meaning

s_temp = bar spacing for temperature steel (mm); A_b = bar area; A_s,temp = area per metre

Watch out

Maximum spacing for temperature steel: s ≤ min(5h, 450 mm). Tighter spacing required than for main steel.

When to use

Convert A_s,temp to practical bar spacing

Common values

Value

0.0018

Symbol

ρ_temp

Quantity

Temperature ratio (f_y = 415 MPa)

Value

0.0020

Symbol

ρ_temp

Quantity

Temperature ratio (f_y = 275 MPa)

Value

min(3h, 450) mm

Symbol

s_max

Quantity

Max spacing main steel

Value

min(5h, 450) mm

Symbol

s_temp,max

Quantity

Max spacing temp steel

Important facts

  • Temperature steel is perpendicular to main flexural steel (one-way slabs: temperature steel runs parallel to span, main steel perpendicular).
  • Maximum spacing: main steel ≤ min(3h, 450 mm); temperature steel ≤ min(5h, 450 mm).
  • If computed A_s,main < A_s,temp, use A_s,temp and adjust spacing for both directions.
  • Slab shrinkage ratio ρ_temp is constant per NSCP — does NOT depend on moment or span.
  • Two-way slabs require temperature steel in BOTH directions (each way gets minimum ρ_temp).

Key definitions

Shrinkage & Temperature Cracking

Example

A slab 175 mm thick will shrink ~0.04–0.06% of its length; temperature steel prevents one large crack and creates many small ones.

Uncontrolled cracking in concrete slabs due to drying shrinkage and thermal expansion/contraction; minimum reinforcement (ρ = 0.0018) distributes cracks and limits crack width.

Diagrams to know

  • Slab reinforcement plan showing main steel and perpendicular temperature steel with spacings.
  • Cross-section showing location of temperature bars relative to main bars.

Two-Way Slabs: Coefficient Method (Slabs on Beams)

Formulas

M_x = C_x × w × L_s²; M_y = C_y × w × L_s²

Meaning

M_x, M_y = moments in two directions (kN·m/m); C_x, C_y = tabulated coefficients (NSCP Table); w = uniform service load (kN/m²); L_s = shorter span (m)

Watch out

Use SHORTER span L_s, not longer span. Coefficients depend on aspect ratio L_long/L_short and which edges are continuous.

When to use

Two-way slab supported on all four sides by stiff beams; use tabulated coefficients for specific edge condition

Common values

Value

0.5 to 2.0

Symbol

L_long / L_short

Quantity

Typical aspect ratio range

Important facts

  • Coefficients are tabulated in NSCP Section 2.11 (or ACI 318, Table 13.6) for various aspect ratios (0.5 to 2.0) and edge conditions.
  • Common edge conditions: simple support (S), continuous (C); typical cases: 4 continuous edges, 3 continuous, 2 opposite continuous, etc.
  • After calculating moments M_x and M_y, design each direction as a one-way slab per metre width (same procedure as one-way flexural design).
  • Deflection checks less commonly required for thin slabs if minimum thickness is met.
  • Shear in two-way slabs around concentrated loads requires special treatment (punching shear); not covered in basic coefficient method.

Key definitions

Coefficient Method

Example

4.0 m × 3.0 m slab (L_short = 3.0 m) with all edges continuous and w = 6 kN/m² gives M_x and M_y from NSCP coefficient tables.

Empirical moment distribution for two-way slabs on beams; moments determined from tables based on aspect ratio and boundary conditions; simple and conservative.

Diagrams to know

  • Two-way slab panel showing principal directions (x and y), moment distribution pattern.
  • Moment coefficient table layout (rows: aspect ratios; columns: edge conditions; cells: C_x, C_y values).

Two-Way Slabs: Direct Design Method (DDM) — Flat Plates/Slabs on Columns

Formulas

M_o = (w_u × L_2 × L_n²) / 8

Meaning

M_o = total static moment (kN·m per strip); w_u = factored load (kN/m²); L_2 = span perpendicular to direction of analysis (m, center-to-center); L_n = clear span (m, face-to-face of supports) in direction being analyzed

Watch out

Use FACTORED load w_u, not service load. L_n is CLEAR span (subtract column width); L_2 is full span center-to-center. Sign error: M_o is always positive (magnitude).

When to use

DDM for flat plate/slab on columns (no beams); compute total moment for each strip, then distribute to column/middle strips

M_column = 0.75 × M_o × ν; M_middle = 0.25 × M_o × ν

Meaning

M_column, M_middle = moments allocated to column and middle strips; ν = distribution factor (fraction of M_o); typical ν ≈ 1.0 for rectangular panels

Watch out

Distribution depends on geometry and loading; values given here are approximate. Consult NSCP Section 2.12 or ACI 318 for exact ν.

When to use

After computing M_o, split into column strip (typically 60–75%) and middle strip (25–40%)

Common values

Value

10–12 kN/m²

Symbol

w_u

Quantity

Typical factored load (residential)

Value

12–16 kN/m²

Symbol

w_u

Quantity

Typical factored load (office)

Important facts

  • DDM is simpler than Equivalent Frame Method (EFM) but less accurate for irregular geometry.
  • Limitation: DDM applies to regular rectangular slab panels; panels with significantly different spans or asymmetric loading require EFM.
  • Negative moments occur over columns (critical for punching shear); positive moments at mid-span.
  • Total static moment M_o is a reference value; actual moments vary across the strip.
  • After design, check SHEAR around columns (punching shear per ACI 318 Section 8.6) — often governs flat-plate thickness more than bending.

Key definitions

Direct Design Method (DDM)

Example

5 m × 4 m flat slab, clear spans L_nx = 4.8 m, L_ny = 3.8 m, w_u = 12 kN/m² → M_o,x = (12 × 4 × 4.8²) / 8 = 55.3 kN·m.

Simplified procedure for flat plates/slabs on columns; computes total static moment M_o, then distributes to column and middle strips without detailed frame analysis.

Column Strip

Example

For L_2 = 4 m, column strip width ≈ 1 m; carries majority of moment.

Central portion of slab above/below column (typically width = min(L_2/4, L_n/4)); resists ~60–75% of total moment.

Middle Strip

Example

Remaining 2 m width on each side of the 1 m column strip.

Remaining portion of slab between column strips; resists ~25% of total moment; lighter reinforcement.

Diagrams to know

  • Flat slab plan view showing column grid, span directions (L_2, L_n), column strips, and middle strips.
  • Moment distribution diagram across the span showing parabolic shape of M (positive mid-span, negative over columns).
  • Column strip vs middle strip moment allocation sketch.

Key Equations & Conversions

Diagrams to know

  • Moment diagram for continuous vs simply-supported beams/slabs (shape of M affects minimum thickness).

Reactions or equations

M (kN·m) × 10⁶ = M (N·mm)

Note

Always ensure units match: if R_n formula uses d in mm, M_u must be in N·mm.

Conditions

Unit conversion for moment; essential when using R_n = M_u / (φ b d²)

A_bar × 1000 / A_s = s (mm spacing)

Note

Example: 10 mm φ bar (78.5 mm²) with A_s = 315 mm²/m → s = 249 mm ≈ 250 mm.

Conditions

Converting per-metre steel area to practical bar spacing; A_bar in mm², A_s in mm²/m

Aspect Ratio = L_long / L_short

Note

Always measure span center-to-center or clear span consistently.

Conditions

If ≥ 2.0 → one-way; if < 2.0 → two-way

h_min = (L / C) × (0.4 + f_y / 700)

Note

Round up to nearest 10 or 25 mm for practical thickness. This h_min assumes fy = 415 MPa baseline.

Conditions

Deflection control; C = 20 (SS), 24 (1EC), 28 (2EC), 10 (cantilever); f_y in MPa

Must remember

ASPECT RATIO CLASSIFICATION: Always divide LONGER by SHORTER span. If ≥ 2.0 → one-way; < 2.0 → two-way. A slab on only two opposite sides is ALWAYS one-way, regardless of ratio.

Order

1

MINIMUM THICKNESS FORMULA: h_min = (L/C) × (0.4 + f_y/700). Use clear or effective span. C = 20 (SS), 24 (1EC), 28 (2EC), 10 (cantilever). Adjust for f_y ≠ 415 MPa. If h < h_min, perform deflection check.

Order

2

SHRINKAGE/TEMPERATURE STEEL ALWAYS REQUIRED: ρ_temp = 0.0018 (f_y = 415 MPa) or 0.0020 (f_y = 275 MPa). A_s,temp = ρ_temp × 1000 × h (full thickness). If A_s,flexural < A_s,temp, USE MINIMUM.

Order

3

PER-METRE DESIGN PROCEDURE (One-Way): (1) Factor moment M_u → (2) Compute R_n = M_u / (0.90 × 1000 × d²) → (3) Solve for ρ → (4) Get A_s = ρ × 1000 × d (mm²/m) → (5) Convert to bar spacing s = A_bar × 1000 / A_s. Keep units: if M_u in kN·m, convert to N·mm.

Order

4

BAR SPACING LIMITS: Main steel s ≤ min(3h, 450 mm); Temperature steel s ≤ min(5h, 450 mm). If calculated spacing exceeds limit, reduce it. If spacing becomes impractically small, use larger bar size.

Order

5

TWO-WAY COEFFICIENT METHOD: M_x = C_x × w × L_s²; M_y = C_y × w × L_s². Use SERVICE load w (or factor to w_u), SHORTER span L_s, and coefficients from NSCP Table 2.11 based on aspect ratio and edge condition. Design each direction as one-way.

Order

6

TWO-WAY DDM FOR FLAT PLATES: M_o = (w_u × L_2 × L_n²) / 8. Use FACTORED load w_u, clear span L_n in direction analyzed, perpendicular span L_2 (center-to-center). Distribute M_o to column strip (~75%) and middle strip (~25%); design each for bending and check punching shear.

Order

7

MINIMUM STEEL RATIO GOVERNING: Thin slabs with small moments often have A_s,minimum (from shrinkage/temperature, ρ = 0.0018) control the design. Always check A_s,calculated ≥ A_s,minimum. If not, use minimum and adjust spacing downward.

Order

8

EFFECTIVE DEPTH d: Calculate d = h − cover − bar diameter/2. For slabs, cover is typically 20–30 mm on bottom, 30–40 mm on top (depending on environment and code). Small d significantly increases R_n and ρ; verify cover in design assumptions.

Order

9

COMMON BOARD-EXAM MISTAKES: (1) Wrong span ratio (short/long instead of long/short). (2) Forgetting f_y adjustment on h_min. (3) Missing shrinkage/temperature minimum. (4) Using center-to-center span instead of clear span for h_min. (5) Confusion between per-metre steel A_s and bar spacing s. (6) Over-reinforcement (ρ > ρ_balanced) — section fails suddenly. Check bounds 0.0014 ≤ ρ ≤ ρ_balanced.

Order

10

Last minute tips

ASPECT RATIO TRAP: Many students flip long/short. Quick check: if one span is obviously much longer (e.g., 6 m vs 2.4 m), ratio = 2.5 → one-way. If both spans similar (e.g., 4 m vs 3.5 m), ratio = 1.14 → two-way. Never assume — calculate both ways if unsure.

Order

1

MINIMUM THICKNESS FREQUENCY: On nearly every board problem, the chosen h ends up being dictated by h_min, not by moment capacity. Always compute h_min as your FIRST step; if candidate h ≥ h_min, you're safe. If h < h_min, flag for deflection check (rarely required if h is chosen correctly).

Order

2

UNIT CONVERSION FOR R_n: If problem gives moment in kN·m and you forget to convert to N·mm, your R_n will be off by 10⁶. Always double-check: R_n = M_u(N·mm) / [0.90 × 1000(mm) × d²(mm²)]. Result in MPa.

Order

3

BAR SPACING QUICK CALCULATION: s = (A_bar × 1000) / A_s is fast. Memorize key bar areas: φ10 = 78.5 mm², φ12 = 113 mm², φ16 = 201 mm². If A_s = 315 mm²/m and φ10 → s ≈ 250 mm (handy to verify). If s_calc > min(3h, 450), reduce it.

Order

4

TWO-WAY COEFFICIENT TABLE OFTEN PROVIDED: On the exam, if you see a two-way slab, the problem usually includes a coefficient table or directs you to NSCP Table 2.11. Use the table, don't try to memorize coefficients. BUT be sure to use shorter span L_s, not longer span, in M = C w L_s².

Order

5

Comparison tables

One-Way vs Two-Way Slabs: Quick Reference

PropertyOne-Way SlabTwo-Way Slab
Aspect Ratio (L_long / L_short)≥ 2.0< 2.0
Support ConditionTwo opposite sides OR any lengthAll four sides on stiff supports
Bending DirectionOne direction (across short span)Both directions (x and y)
Design MethodPer-metre strip (b = 1000 mm); flexural formulas for beamCoefficient method (beams) or DDM/EFM (flat plate)
Typical MomentsM_u based on L_short²M_x = C_x w L_s²; M_y = C_y w L_s²
Temperature SteelOne direction (perpendicular to main)Both directions (each way min ρ = 0.0018)
Board-Exam FrequencyVery common; ~60% of slab problemsCommon; ~40%; often with coefficient table provided

Minimum Thickness by Support Condition (f_y = 415 MPa Baseline)

Support ConditionCoefficient Ch_min = L/CExample (L = 4.0 m)
Simply Supported20L/20200 mm
One End Continuous24L/24167 mm
Both Ends Continuous28L/28143 mm
Cantilever10L/10400 mm

Common Bar Areas & Spacings for Slabs

Bar Size (mm φ)Area (mm²)Spacing for A_s = 315 mm²/mSpacing for A_s = 400 mm²/mSpacing for A_s = 500 mm²/m
1078.5249 mm196 mm157 mm
12113.1359 mm283 mm226 mm
16201.1638 mm503 mm402 mm

Diagrams

Slab Classification & Design Method Decision Tree

Step-by-step flowchart to classify a slab as one-way or two-way and select the correct design method. Branches on support condition, aspect ratio, and support type (beams vs columns).

One-Way Slab Flexural Design Formula Map

Mind map showing the hierarchical five-step process for designing one-way slab flexural steel, from factored moment through bar spacing and limits.

Minimum Thickness (Deflection Control) – Quick Calculator

Flowchart guiding selection of support condition coefficient and yield strength adjustment to compute minimum thickness quickly. Common values highlighted.

Slab Design Workflow State Diagram

State diagram tracking the design workflow from initial classification through final bar spacing, showing decision points and state transitions.

Typical Slab Problem Distribution on Board Exams

Pie chart showing typical distribution of slab problem types on PRC licensure exams. One-way and two-way flexural design dominate; minimum thickness and special cases less frequent.

Reinforced Concrete Slabs is chapter 5 of 7 in the Reinforced & Prestressed Concrete part of Super Tutor's CELE review. The Civil Engineer Licensure Examination is given by Professional Regulation Commission (PRC) — Board of Civil Engineering; its dates, format and passing rules are on the CELE page. See the CELE guide.

Study Reinforced Concrete Slabs in the Super Tutor app

Super Tutor's CELE review has every chapter in 11 study formats, practice quizzes at three difficulty levels and an AI tutor, plus full CELE mock exams. Start free — 5-day trial, no card.