CELE Structural Theory & Analysis — Loads and Load Combinations (NSCP)Revision Notes
Condensed revision notes for Loads and Load Combinations (NSCP), built for the final weeks before the CELE 2026. These are the distilled key points you need when there is no time left for full study notes — just the concepts, formulas, and traps Professional Regulation Commission (PRC) — Board of Civil Engineering tests.
Exam context
The Civil Engineer Licensure Examination is conducted by Professional Regulation Commission (PRC) — Board of Civil Engineering and is scheduled for May and November 2026. The Structural Theory & Analysis subtest is marked as "Core" in the official pattern, and Loads and Load Combinations (NSCP) appears in position 6th of 6 in the CELE Structural Theory & Analysis review rotation. Passing mark: 70% weighted average, no sub-test below 50%. Recent CELE 2026 papers have drawn roughly a meaningful share of questions from this subject.
Loads and Load Combinations (NSCP) - Revision Notes
Every structural member must be designed to safely carry the loads it will experience during its service life. Before any design calculation begins, the engineer must identify, quantify, and combine loads according to the governing code. In the Philippines, this is the National Structural Code of the Philippines (NSCP 2015), Volume I. This chapter is consistently tested in the PRC Civil Engineer Licensure Examination under Structural Theory & Analysis and is the entry point for all concrete (NSCP/ACI 318) and steel (NSCP/AISC 360) design problems. Mastery of load types, tributary-area concepts, and both LRFD and ASD load combinations is non-negotiable for exam success.
Sections
Formulas
Example
Beams spaced 3 m on center; slab DL = 4 kPa, LL = 2 kPa. → wD = 4 × 3 = 12 kN/m; wL = 2 × 3 = 6 kN/m
Formula
w = q × s
Variables
w = distributed line load on beam (kN/m); q = area load (kPa = kN/m²); s = beam spacing or tributary width (m)
Application
Converts a floor/slab area load to a beam line load using tributary width. Applies to both dead and live components.
Example
Column with 6 m × 6 m tributary; DL = 5 kPa, LL = 3 kPa. → PD = 5 × 36 = 180 kN; PL = 3 × 36 = 108 kN
Formula
P = q × A_t
Variables
P = axial load on column (kN); q = area load (kPa); A_t = tributary area of column (m²)
Application
Converts area loads to column axial forces. Tributary area is bounded at mid-spans in both directions.
Exam Tips
- NSCP Table 205-1 minimum live loads are frequently given in problems; memorize the common values: residential 1.9 kPa, office 2.4 kPa, assembly 4.8 kPa.
- When a problem says 'interior beam,' the tributary width = full bay spacing. 'Edge beam' = half bay spacing.
- For a two-way slab, tributary areas to beams are trapezoidal or triangular — if not specified, treat one-way and use s as the shorter direction.
Key Points
- Dead load (D): permanent, gravity, self-weight of structure plus all permanently attached items (finishes, fixed MEP, partitions). Highly predictable — lowest load factor in combinations.
- Live load (L): variable occupancy loads — people, furniture, movable equipment. NSCP Table 205-1 gives minimum values by occupancy: residential 1.9 kPa, office 2.4 kPa, classroom 1.9–2.9 kPa, assembly areas 4.8 kPa.
- Roof live load (Lr): temporary loads on roofs from maintenance workers and equipment. Distinct from ordinary live load.
- Wind load (W): depends on basic wind speed, exposure category, height above ground, and building shape/pressure coefficients (NSCP Section 207).
- Earthquake load (E): seismic; the Philippines lies along the Pacific Ring of Fire — E often GOVERNS lateral design, especially in Seismic Zones 4 and 4-A.
- Rain load (R): ponding from blocked drains on flat roofs.
- Snow (S): negligible in most Philippine locations; rarely tested.
- The companion action factor f1 for L in LRFD combos 3–5: f1 = 1.0 for assembly areas, garages, and L > 4.8 kPa; f1 = 0.5 for all other occupancies.
Definitions
Term
Dead Load (D)
Definition
The weight of all permanent structural and non-structural components — slabs, beams, columns, walls, finishes, and fixed equipment.
Importance
Always present; appears in every load combination. Its predictability earns it the lowest uncertainty factor (1.2 in LRFD vs 1.6 for L).
Term
Live Load (L)
Definition
Loads produced by the use and occupancy of a structure, excluding construction loads and environmental loads (wind, earthquake, snow).
Importance
Highly variable in time and space; governed by NSCP Table 205-1. The dominant variable load in most gravity combinations.
Term
Tributary Area
Definition
The floor area that is geometrically closest to a given member — bounded by mid-spans to adjacent members on all sides.
Importance
The key concept for routing loads from slabs to beams and from beams to columns. Interior beams take full spacing; edge beams take half-spacing.
Section Title
Load Types and Their Characteristics
Common Mistakes
- Using the full beam span as tributary width instead of the beam spacing (s) — the span is the length along the beam, the spacing is the tributary width perpendicular to it.
- Forgetting to add self-weight of the beam itself to the dead load when computing total wD.
- Using an occupancy live load for a roof — roof live load Lr is separate from floor LL.
- Confusing kPa (kN/m²) and kN/m — always check units when multiplying area loads by lengths.
- Assuming snow or rain govern in the Philippines — the seismic load E almost always governs lateral design in Philippine seismic zones.
Formulas
Example
w = 24 kN/m, L = 6 m → R = (24 × 6)/2 = 72 kN per support
Formula
R = (w × L) / 2
Variables
R = end reaction/shear of a simply supported beam (kN); w = uniform line load (kN/m); L = beam span (m)
Application
Finds the concentrated load delivered to the girder or column supporting a beam end.
Example
wu = 24 kN/m, L = 6 m → Mu = 24(6²)/8 = 108 kN·m
Formula
M_max = (w × L²) / 8
Variables
M_max = maximum midspan moment (kN·m); w = uniform line load (kN/m); L = span (m)
Application
Design moment for a simply supported beam with UDL — the most common beam model in board exams.
Exam Tips
- Always draw a quick floor plan sketch and mark tributary boundaries before computing any loads — this prevents errors on edge vs interior members.
- For columns: count the number of floors above, multiply the per-floor tributary load by the number of floors as a quick check.
- Beam self-weight can be estimated: for RC beams, unit weight of concrete γ = 23.5–24 kN/m³; beam self-weight per meter = γ × b × h.
Key Points
- Tributary area principle: each member carries the load from the region geometrically closer to it than to any other parallel member.
- Interior beam: tributary width = full spacing s (half-bay each side → total = s).
- Edge/perimeter beam: tributary width = s/2 (one-sided).
- Corner column: At = (s1/2)(s2/2). Interior column: At = s1 × s2. Edge column: At = (s1/2)(s2) or (s1)(s2/2). Always sketch the plan and draw the tributary boundaries.
- For a uniformly loaded simply supported beam: total reaction = (w × L)/2 at each support → this becomes the beam-end shear transferred to the girder or column.
- Multi-story buildings: column loads accumulate floor-by-floor (cumulative tributary load).
Definitions
Term
Tributary Width
Definition
The width of slab (perpendicular to a beam's span) that delivers its load to that beam; equal to the sum of the two half-spacings on each side of the beam.
Importance
Directly multiplies the area load to give line load w. Getting this wrong cascades error through all downstream calculations.
Term
Cumulative Column Load
Definition
The total axial load on a column at a given story, equal to the sum of tributary floor loads from all floors above, plus the column self-weight.
Importance
Critical for column design in multi-story buildings; the lower-story columns carry the largest axial forces.
Section Title
Tributary Area — Routing Loads to Members
Common Mistakes
- Assigning full bay spacing to an edge beam instead of half — this doubles the load on the edge beam erroneously.
- Forgetting to include the beam's own self-weight as part of dead load before computing wD.
- For a two-span continuous beam, using simple-beam tributary areas — the reactions differ; use proper analysis or moment distribution.
- Mixing up 'beam span' (along beam length) with 'beam spacing' (center-to-center distance between parallel beams).
Formulas
Example
D = 20 kN/m, L = 0 → U1 = 1.4(20) = 28 kN/m
Formula
U₁ = 1.4D
Variables
U = factored load effect; D = dead load effect
Application
Governs only when dead load is unusually large and there is essentially no live load (e.g., heavy equipment foundations).
Example
wD = 12 kN/m, wL = 6 kN/m → wu = 1.2(12) + 1.6(6) + 0 = 14.4 + 9.6 = 24 kN/m
Formula
U₂ = 1.2D + 1.6L + 0.5(Lr or R)
Variables
D = dead; L = live; Lr = roof live; R = rain
Application
GOVERNING combo for most floor beams and columns with significant live load. Most commonly used in board exam gravity problems.
Example
D = 10, Lr = 6, L = 4 kN/m → U3 = 1.2(10) + 1.6(6) + 1.0(4) = 12 + 9.6 + 4 = 25.6 kN/m
Formula
U₃ = 1.2D + 1.6(Lr or R) + (1.0L or 0.5W)
Variables
Lr = roof live; R = rain; L = floor live; W = wind
Application
Governs when roof live or rain load is large relative to floor live load.
Example
PD = 180, PL = 108, PW = 60 kN → Pu = 1.2(180) + 1.0(60) + 1.0(108) = 216 + 60 + 108 = 384 kN
Formula
U₄ = 1.2D + 1.0W + 1.0L + 0.5(Lr or R)
Variables
W = wind load effect
Application
Governs for structures subject to significant wind alongside gravity loads (tall buildings, open structures).
Example
PD = 180, PL = 108, PE = 90 kN → Pu = 1.2(180) + 1.0(90) + 1.0(108) = 216 + 90 + 108 = 414 kN
Formula
U₅ = 1.2D + 1.0E + 1.0L
Variables
E = earthquake load effect
Application
Critical for Philippine structures in seismic zones — earthquake + gravity. Often governs for column design.
Example
PD = 180 kN (compression), PW = -200 kN (tension/uplift) → Pu = 0.9(180) + 1.0(-200) = 162 - 200 = -38 kN (net tension!)
Formula
U₆ = 0.9D + 1.0W
Variables
Use when wind causes uplift or overturning — the 0.9 factor reduces the stabilizing effect of dead load.
Application
Governs for tension in anchor bolts, uplift on roof systems, overturning of retaining walls under wind.
Example
PD = 180 kN, PE = -220 kN → Pu = 0.9(180) - 220 = 162 - 220 = -58 kN net tension
Formula
U₇ = 0.9D + 1.0E
Variables
Use when seismic causes net uplift or overturning — critically important in PH seismic design.
Application
Governs for tension at column bases, rocking of shear walls, overturning moments from seismic.
Exam Tips
- For gravity-only problems (no wind, no seismic): evaluate only U1, U2, U3, U4 (with W=0). U2 almost always governs when L is significant.
- For problems with wind: check U4 (1.2D+1.0W+1.0L) AND U6 (0.9D+1.0W). U6 may govern for uplift.
- Memorize the factored load factors: D gets 1.2 (or 0.9 for uplift), L gets 1.6 (primary) or 1.0 (companion), W and E get 1.0.
- Board exams often give wD and wL in kN/m and ask for wu and Mu — apply U2: wu = 1.2wD + 1.6wL, then Mu = wuL²/8.
- When the problem asks for 'design axial load' without specifying method, default to LRFD (Pu) unless ASD is explicitly stated.
Key Points
- LRFD (Load and Resistance Factor Design) amplifies loads with factors > 1.0 and reduces nominal strength with φ factors (φ < 1.0). The factored load demand ≤ factored strength.
- Gravity combinations are the most common in board problems. Combo 2 (1.2D + 1.6L) governs for most floor systems with large live loads.
- Combos 6 and 7 (0.9D + 1.0W and 0.9D + 1.0E) capture the UPLIFT condition — when wind or seismic acts upward and dead load resists it. The 0.9 factor reduces the 'helpful' dead load conservatively.
- The companion action factor f1 for L: use 1.0L for assembly areas (L > 4.8 kPa, garages); use 0.5L for all other occupancies in combos 3, 4, and 5.
- For seismic: E includes both horizontal (Eh) and vertical (Ev) components per NSCP Section 208. In simplified form, E = Eh ± Ev.
- Always evaluate ALL applicable combinations and use the one producing the most severe effect (max moment, max shear, max axial — can differ per combination).
Definitions
Term
LRFD (Load and Resistance Factor Design)
Definition
A design philosophy where factored loads (demand) must not exceed factored nominal strength (capacity): ΣγᵢQᵢ ≤ φRn. Load factors γᵢ > 1.0 account for load variability; resistance factor φ < 1.0 accounts for strength variability.
Importance
The primary design method in NSCP 2015, ACI 318, and AISC 360. Required understanding for all structural design exam problems.
Term
Companion Action Factor (f₁)
Definition
The factor applied to L in LRFD combos 3–5 when live load acts simultaneously with roof live, wind, or seismic. f₁ = 1.0 for assembly, garages, L > 4.8 kPa; f₁ = 0.5 for all others.
Importance
Reduces L in combinations where it is the secondary (companion) rather than primary load. Missing this costs points — many review materials conservatively default to 1.0L.
Term
Uplift Combination
Definition
LRFD combos U₆ (0.9D + 1.0W) and U₇ (0.9D + 1.0E) — used when wind or seismic tends to lift or overturn the structure, where dead load acts as a beneficial (stabilizing) load.
Importance
Frequently missed by examinees; critical for foundations, anchor bolts, and roof systems. The reduced 0.9D factor is intentionally conservative for the stabilizing action.
Section Title
LRFD Load Combinations (NSCP 2015)
Common Mistakes
- Applying only Combo U2 (1.2D + 1.6L) and ignoring the wind/seismic combinations — the problem may require checking all combos.
- Forgetting Combos U6 and U7 entirely — uplift/overturning can make an element go from compression to tension, requiring a completely different design.
- Using f₁ = 1.0L in combo U4 for a residential floor (correct f₁ = 0.5) — this overestimates the load but may cost accuracy points.
- Adding E and W in the same combination — NSCP does not combine E and W simultaneously; each is considered independently in its respective combination.
- Using LRFD factored loads (Pu, Mu, Vu) with allowable stress design tables — always match design method with the correct load combination set.
Formulas
Example
Dead load only case: wD = 15 kN/m → w_service = 15 kN/m
Formula
ASD-1: D
Variables
D = dead load effect only
Application
Rarely governs for members; may control for foundations with large dead load and negligible live load.
Example
wD = 12, wL = 6 kN/m → w = 18 kN/m; M = 18(6²)/8 = 81 kN·m (vs Mu = 108 kN·m LRFD)
Formula
ASD-2: D + L
Variables
D = dead load; L = live load
Application
Governing ASD gravity combo for most floor systems. The service load equivalent of LRFD Combo 2.
Example
wD = 8, wLr = 4 kN/m → w = 12 kN/m
Formula
ASD-3: D + (Lr or R)
Variables
Lr = roof live; R = rain
Application
Governs for roof members when only roof live or rain acts with dead load.
Example
D = 10, L = 8, Lr = 4 kN/m → w = 10 + 0.75(8) + 0.75(4) = 10 + 6 + 3 = 19 kN/m
Formula
ASD-4: D + 0.75L + 0.75(Lr or R)
Variables
0.75 = simultaneous load reduction factor
Application
Use when both floor live and roof live act simultaneously; 0.75 reduces each to account for improbability of both at maximum.
Example
PD = 180 kN, PW = 100 kN → P = 180 + 0.6(100) = 180 + 60 = 240 kN
Formula
ASD-5a: D + 0.6W; ASD-5b: D + 0.7E
Variables
0.6W and 0.7E are the ASD-equivalent wind and seismic
Application
Wind or seismic acting with dead load only (no live load companion). Check separately for 5a and 5b.
Example
D=10, L=8, W=6, Lr=4 kN/m → w = 10 + 0.75(8) + 0.75(0.6×6) + 0.75(4) = 10+6+2.7+3 = 21.7 kN/m
Formula
ASD-6: D + 0.75L + 0.75(0.6W) + 0.75(Lr or R)
Variables
Full combination of gravity + wind + roof live; seismic companion: D + 0.75L + 0.75(0.7E)
Application
Most comprehensive gravity + lateral ASD combo. Governs for elements subject to all loads simultaneously.
Example
PD = 180 kN, PW = -150 kN (uplift) → P = 0.6(180) + 0.6(-150) = 108 - 90 = +18 kN (still compression, OK)
Formula
ASD-7a: 0.6D + 0.6W; ASD-7b: 0.6D + 0.7E
Variables
0.6D reduces the stabilizing dead load for uplift checks
Application
Uplift/overturning check under wind or seismic. The 0.6D mirrors the LRFD 0.9D concept for ASD.
Exam Tips
- ASD vs LRFD comparison for the same beam: LRFD always gives a larger design moment/force than ASD for the same loads — confirm this ratio to check your arithmetic.
- For a beam with wD = 12 and wL = 6 kN/m: LRFD wu = 24 kN/m; ASD w = 18 kN/m. The LRFD/ASD ratio ≈ 1.33, which is typical for D:L ≈ 2:1.
- When the exam says 'service loads' or 'working loads' — use ASD combinations. 'Factored loads' or 'design loads' — use LRFD.
- ASD Combo 5 uses 0.7E (not 1.0E). Many reviewees use 1.0E — this is ONLY for LRFD. The 0.7E in ASD is a calibration factor.
Key Points
- ASD (Allowable Stress Design) uses service (unfactored) loads; the structure is checked against an allowable stress = Fu/FS or Fy/FS where FS is a factor of safety.
- ASD Combo 1 (D alone) and Combo 2 (D + L) are the most common gravity ASD combinations.
- The 0.75 factor in Combos 4 and 6 reflects the reduced probability that all loads reach their maximums simultaneously.
- ASD uplift combos use 0.6D (analogous to LRFD 0.9D) — the reduced dead load is intentional for the stabilizing action.
- Wind appears as 0.6W and seismic as 0.7E in ASD — these are NOT the same W and E as in LRFD. The reduction factors make ASD wind/seismic comparable to LRFD in terms of reliability.
- Choose ONE design philosophy (LRFD or ASD) and apply it consistently — never mix factored and service loads in the same analysis.
Definitions
Term
ASD (Allowable Stress Design)
Definition
A design philosophy where actual stresses under service loads must not exceed allowable stresses: f_actual ≤ F_allowable = F_nominal / FS. No load factors are applied; safety margin is on the resistance side.
Importance
Still used for certain structural applications and referenced in AISC 360 ASD provisions. Board exams test both LRFD and ASD for steel design.
Term
Simultaneous Load Factor (0.75)
Definition
The ASD reduction factor applied when three or more load types act simultaneously (e.g., D + 0.75L + 0.75Lr), reflecting the reduced probability that all loads reach their code-maximum values at the same time.
Importance
Can make ASD Combo 4 or 6 less critical than Combo 2 (D + L), depending on magnitudes. Must be explicitly applied.
Section Title
ASD Load Combinations (NSCP 2015)
Common Mistakes
- Applying the 0.75 factor in ASD Combo 4 to the dead load — the 0.75 factor applies only to L and Lr/R, NOT to D.
- Confusing 0.6W (ASD) with 1.0W (LRFD) — ASD already applies the 0.6 factor to make wind comparable to LRFD in reliability.
- Using ASD service moment (M = wL²/8) directly in an LRFD design table — the design moment must match the design philosophy.
- Forgetting ASD-7 uplift combos (0.6D + 0.6W or 0.6D + 0.7E) when checking tension at foundations.
Formulas
Example
EXAMPLE 2: wu = 1.2(12) + 1.6(6) = 14.4 + 9.6 = 24 kN/m; L = 6 m → Mu = 24(36)/8 = 108 kN·m
Formula
Mu = wu × L² / 8 (for simply supported beam with UDL)
Variables
Mu = factored design moment (kN·m); wu = factored uniform line load (kN/m) from governing LRFD combo; L = beam span (m)
Application
The most frequently used beam moment formula in board exams. Always confirm simply supported boundary conditions.
Example
EXAMPLE 3: PD = 180, PL = 108 kN → Pu = 1.2(180) + 1.6(108) = 216 + 172.8 = 388.8 kN
Formula
Pu = 1.2PD + 1.6PL (LRFD Combo 2, gravity only)
Variables
Pu = factored axial load (kN); PD = dead load axial force; PL = live load axial force
Application
Interior column design under gravity loads only. Check also U1 = 1.4PD if PL is very small.
Exam Tips
- QUICK CHECK for gravity beam: wu = 1.2wD + 1.6wL. If wD:wL ≈ 2:1, expect wu ≈ 1.33 × (wD + wL).
- For column with all loads (D, L, W): check at minimum: U2 (max compression, no wind), U4 (D+W+L, compression side), U6 (uplift, W opposite to D).
- Mu = wuL²/8 → Mu varies with L² — doubling the span quadruples the moment. This is why long-span beams are often the critical design element.
- Always state units clearly in the exam — kN·m for moment, kN for force, kN/m for line load, kPa for area load.
Key Points
- Example 1: Beam tributary line load — convert area loads to line loads using tributary width.
- Example 2: Factored beam moment (LRFD) — apply governing LRFD combo and compute Mu.
- Example 3: Column axial load (LRFD vs ASD) — compute Pu and P_service from tributary area loads.
- Example 4: Column with wind — check all relevant LRFD combos including uplift.
- Board exam problems typically present area loads (kPa) + geometry → ask for factored line load, design moment, or design axial force.
Definitions
Term
Design Moment (Mu)
Definition
The maximum factored bending moment that a beam section must be designed to resist. Mu ≤ φMn where φ = 0.90 for flexure (ACI 318 / NSCP) and Mn is the nominal moment strength.
Importance
The fundamental demand quantity in beam design. Always computed from the governing factored load combination.
Term
Design Axial Force (Pu)
Definition
The maximum factored axial compressive (or tensile) force that a column section must be designed to resist. Pu ≤ φPn.
Importance
Fundamental for column design. Must check all combinations — different combos may give compression, reduced compression, or even tension.
Section Title
Worked Board-Style Examples
Common Mistakes
- Using M = wL²/8 for a continuous beam — this formula is ONLY for simply supported beams. For continuous beams, use moment coefficients or matrix methods.
- Forgetting that the beam's own self-weight contributes to wD — problems may give slab dead load but expect you to add beam self-weight.
- For columns with wind: students often check only U2 (gravity) and U4 (gravity + wind compression) but miss U6 (0.9D + W for potential uplift or tension).
Connections
- NSCP Loads → ACI 318 RC Beam Design: The factored loads (Mu, Vu, Pu) from NSCP LRFD combos are directly used in ACI 318 beam/column strength equations (φMn ≥ Mu, φVn ≥ Vu, φPn ≥ Pu). You cannot design an RC section without first computing loads.
- NSCP Loads → AISC 360 Steel Design: Same factored loads feed into steel beam flexure (φMn = φZxFy), shear (φVn = φ0.6FyAw), and column compression (φPn via KL/r curves). AISC 360 explicitly supports both LRFD and ASD with separate provisions.
- Tributary Area → Structural Analysis: Once loads are routed to members, they become the applied forces for structural analysis (beams as UDL, girders with point loads, columns with axial loads). The load path concept — slab → beam → girder → column → foundation — is tested in both loads and structural analysis topics.
- Seismic Load (E) → NSCP Section 208 Earthquake Provisions: The E in load combinations links to the seismic design base shear V = CsW, seismic zone, occupancy importance factor, and soil profile. Philippine practice requires familiarity with Seismic Zones 2 to 4-A.
- Wind Load (W) → NSCP Section 207: The W in load combinations is derived from the design wind pressure p = qzGCp, requiring knowledge of basic wind speed map, exposure categories, and pressure coefficients — tested in the structural loads subtopic.
- LRFD vs ASD → Practical Design: Understanding both methods allows the engineer to choose the more economical approach or satisfy a specific code requirement. AISC 360 permits either; ACI 318 is LRFD-only. This connection appears in combined exam items asking students to compare both results.
- RA 544 (Civil Engineering Law) → Professional Practice: While RA 544 governs the practice of civil engineering in the Philippines, the engineer of record is legally responsible for applying the correct code (NSCP) provisions. Understanding that NSCP is the mandatory Philippine standard (not ACI 318 or AISC directly, but adopted by reference) is part of professional competence.
- Dead Load Estimation → Material Properties: Computing dead loads requires knowing unit weights: reinforced concrete 23.5–24 kN/m³, structural steel 77 kN/m³, wood (varies), masonry 17–22 kN/m³. These values appear in NSCP Table 204-1 and are tested alongside load combination problems.
Exam Strategy
For PRC board exam problems on Loads and Load Combinations: (1) READ the problem carefully — identify whether it asks for service (ASD) or factored (LRFD) quantities. 'Design load' or 'factored load' → LRFD; 'service load' or 'working load' → ASD. (2) SKETCH the framing plan — mark tributary boundaries for each member type (interior vs edge beam, interior vs edge vs corner column). (3) COMPUTE area loads first (kPa × m = kN/m for beams; kPa × m² = kN for columns). (4) APPLY all relevant load combinations and IDENTIFY the governing one — do not assume Combo 2 always governs. For wind/seismic problems, always check the uplift combos (0.9D+W or 0.9D+E). (5) COMPUTE the design force/moment — for simply supported beams, Mu = wuL²/8 and Vu = wuL/2. (6) VERIFY units at every step — kPa × m = kN/m (correct); kPa × m² = kN (correct). Time management: load combination problems are typically 3–5 minutes each; if you have practiced the combos and tributary area concept thoroughly, you should not need more than 4 minutes. Allocate extra time for problems combining loads + beam/column design into one multi-part item.
Quick Review Questions
Floor beams are spaced 3.5 m on center and span 8 m. The slab imposes a dead load of 5 kPa and a live load of 2.4 kPa. What is the factored uniform line load wu on an interior beam using NSCP LRFD?
Step 1 — Tributary width = 3.5 m (interior beam, full spacing). Step 2 — wD = 5 × 3.5 = 17.5 kN/m; wL = 2.4 × 3.5 = 8.4 kN/m. Step 3 — Apply NSCP LRFD Combo 2 (governing gravity): wu = 1.2wD + 1.6wL = 1.2(17.5) + 1.6(8.4) = 21.0 + 13.44 = 34.44 kN/m. Note: Check Combo 1: 1.4(17.5) = 24.5 kN/m < 34.44, so Combo 2 governs.
For the beam above (wu = 34.44 kN/m, L = 8 m, simply supported), compute the design moment Mu and maximum design shear Vu.
Mu = wuL²/8 = 34.44(8²)/8 = 34.44(64)/8 = 34.44 × 8 = 275.52 kN·m. Vu = wuL/2 = 34.44(8)/2 = 137.76 kN. These are the quantities entered into φMn ≥ Mu and φVn ≥ Vu checks per ACI 318 or AISC 360.
An interior column has a 5 m × 6 m tributary area. Dead load = 4 kPa, live load = 3 kPa. Compute (a) LRFD factored axial load Pu and (b) ASD service axial load P.
Tributary area At = 5 × 6 = 30 m². PD = 4(30) = 120 kN; PL = 3(30) = 90 kN. (a) LRFD Combo 2: Pu = 1.2(120) + 1.6(90) = 144 + 144 = 288 kN. Check Combo 1: 1.4(120) = 168 kN < 288 kN. ∴ Pu = 288 kN. Wait — recomputing: 1.2(120)=144, 1.6(90)=144 → Pu=288 kN. (b) ASD Combo 2: P = PD + PL = 120 + 90 = 210 kN.
A column carries PD = 250 kN, PL = 120 kN, and PW = ±90 kN (wind can cause compression OR tension). Which NSCP LRFD combinations must be checked, and what are the resulting Pu values?
U2 = 1.2(250) + 1.6(120) = 300 + 192 = 492 kN. U4 = 1.2(250) + 1.0(90) + 1.0(120) = 300 + 90 + 120 = 510 kN (wind additive). U6 compression side: 0.9(250) + 1.0(90) = 225 + 90 = 315 kN. U6 uplift side: 0.9(250) - 1.0(90) = 225 - 90 = 135 kN (still compression — no tension). Governing = U4 = 510 kN for compression design. Always check all combos!
What NSCP LRFD combination is most critical for checking anchor bolt tension (uplift) at a column base subjected to wind?
When wind causes an uplift or overturning force, the dead load acts as a stabilizing (beneficial) load. NSCP uses 0.9D (not 1.2D) to conservatively reduce the dead load's stabilizing contribution. If the net factored force (0.9D + 1.0W) is negative (tension), the anchor bolts must be designed for that tension. Using 1.2D in this case would be unconservative because it overestimates the beneficial dead load.
A roof beam carries wD = 6 kN/m, wLr = 3 kN/m (roof live), and wL = 0 (no floor live). Which NSCP LRFD combo governs and what is wu?
With no floor live load (L = 0), evaluate: U1 = 1.4(6) = 8.4 kN/m. U2 = 1.2(6) + 1.6(0) + 0.5(3) = 7.2 + 0 + 1.5 = 8.7 kN/m. U3 = 1.2(6) + 1.6(3) + (1.0×0 or 0.5×W) = 7.2 + 4.8 = 12.0 kN/m (with no wind). ∴ Combo U3 governs at wu = 12.0 kN/m. The key: when roof live is the primary variable load, U3 (1.6Lr) governs over U2 (only 0.5Lr).
In ASD design, a beam has wD = 10 kN/m and wL = 8 kN/m. What is the service design moment M for a 7 m simply supported span?
ASD Combo 2 (D + L): w = wD + wL = 10 + 8 = 18 kN/m. M = wL²/8 = 18(7²)/8 = 18(49)/8 = 882/8 = 110.25 kN·m. Compare to LRFD: wu = 1.2(10)+1.6(8) = 12+12.8 = 24.8 kN/m → Mu = 24.8(49)/8 = 151.9 kN·m. The LRFD/ASD ratio = 151.9/110.25 ≈ 1.38, which is in the expected range.
What is the difference between the 'companion action factor f1' in NSCP LRFD Combo 4 for a residential building versus an assembly hall?
In NSCP LRFD Combo 4 (1.2D + 1.0W + f1L + 0.5Lr), the companion factor f1 on live load reflects occupancy. For most residential and office buildings, L ≤ 4.8 kPa and the probability that both maximum wind and maximum live act simultaneously is low → f1 = 0.5. For assembly areas (auditoriums, gymnasiums) where L > 4.8 kPa, or for garages, the probability is higher → f1 = 1.0. This distinction appears in board exam problems involving assembly buildings.
Ready to practise for the CELE 2026?
Super Tutor's AI review plan adapts to your weak areas and builds a weekly practice schedule around your target CELE exam date.